Skip to main contentSkip to navigationSkip to contactAccessibility (Alt+A)

Keyboard Shortcuts

  • Alt + A: Open accessibility settings
  • Tab: Navigate to next element
  • Shift + Tab: Navigate to previous element
  • Enter or Space: Activate buttons and links
  • Escape: Close dialogs and menus
  • Arrow keys: Navigate within menus and sliders
  • Home: Go to beginning of list
  • End: Go to end of list
EmersonEIMS — Reliable Power. Without Limits.
HOMEABOUTWHY US
INDUSTRIES
PHASE 4CONTACT
Get Quote

B2BEmersonEIMS serves commercial, industrial, healthcare, telecom, hospitality, government & contractor clients.• Engineering-led • SLA-backed • Documented commissioning

Talk to an engineerWhatsApp+254 768 860 665

Services Directory

View all services →

Power & Generators

  • Cummins Generators (3-yr warranty)
  • Generator Repairs & Maintenance
  • ATS / Changeovers
  • Generator Sales
  • Generator Rental
  • Generator Installation
  • Generator Spare Parts
  • Workshop Repairs & Fabrication
  • Power Interruption Solutions

Renewable & UPS

  • Solar Energy Solutions
  • Commercial / Industrial Solar
  • Solar System Sizing
  • Solar Genius Pro™
  • UPS Systems
  • UPS Lab
  • Solar / UPS Hub
  • Borehole Pumps

Electrical & HVAC

  • Distribution Boards & Panels
  • Motor Rewinding
  • Motors & Drives
  • High-Voltage Systems
  • Diesel Automation
  • Industrial Controls
  • Steel Fabrication
  • AC / HVAC Installation

Specialised & AI Suites

  • Hospital Incinerators
  • Incinerator Construction Guide
  • Building Engineering Suite
  • EIMS PRO Workspace
  • AquaScan Pro™
  • Generator Oracle™
  • Diagnostics Hub
  • Troubleshooting Wizard

Maintenance Hubs

  • Generator Maintenance
  • Solar Maintenance
  • HVAC Maintenance
  • Borehole Maintenance
  • Electrical Maintenance
  • Motors Maintenance
  • Incinerator Maintenance
  • Fabrication & Welding

Resources & Tools

  • Resources & Learning Hub
  • Knowledge Base
  • Technical Bible
  • Power Calculators
  • Fault Code Database
  • Blog & Articles
  • FAQ
  • Emergency Response Guide

Service Areas

  • All Kenya — 47 Counties
  • Nairobi
  • Mombasa
  • Kisumu
  • Nakuru
  • Kiambu
  • All Service Locations
EMERSONEiMS

Engineering-grade reliability for East Africa's critical infrastructure. Power systems built to perform.

  • LinkedIn↗
  • Twitter↗
  • Facebook↗

Company

  • About Us
  • All Services
  • Book a Service
  • Project Gallery
  • Case Studies
  • Industries Served
  • Careers
  • Contact Us

Quick Links

  • Generator Sales
  • Solar Energy
  • Diagnostic Suite
  • Solar / UPS Hub
  • Generator Oracle
  • Knowledge Base
  • FAQ

Contact

  • Nairobi HQEmbakasi, off Airport North Road, Nairobi
    (Near KEMSA Head Office)
  • Department Emails
    • General Inquiriesinfo@emersoneims.com
    • Service Coordinationemersoneimservices@emersoneims.com
    • Generator Deskgenerators@emersoneims.com
    • Solar & UPS Desksolar@emersoneims.com
    • Sally — Direct Accountsally@emersoneims.com
  • Phone
    +254782914717
    +254768860665

© 2026 Emerson EiMS. All rights reserved.

PROTECTED BY GENERATOR ORACLE / EMERSONEIMS
Privacy PolicyTerms of Service
ENGINEERED IN NAIROBI, KENYA
  1. Home
  2. /
  3. Repair Centre
  4. /
  5. inverters
  6. /
  7. Inverter Not Charging Batteries — Diagnosis and Repair

Inverter-chargers and hybrid inverters — charging stage

Inverter Not Charging Batteries — Diagnosis and Repair

Applies to
Inverter-chargers, hybrid and off-grid inverters charging from utility, generator or solar, with lead-acid or lithium banks
Difficulty
intermediate
Competence required
qualified electrician
Diagnosis complexity
Low to moderate. A large share of these are configuration rather than failure, and are resolved without opening the unit.
Electrical system
AC input 240 V 50 Hz nominal; battery DC per system design
Safety classification
stored energy
Author
EmersonEIMS Engineering
Technical review
Mr. Kararaho
Last reviewed
2026-07-27

Scope — read this before relying on the guide

This guide sets out diagnostic method, ranked causes and safety requirements. It deliberately does not state equipment-specific numbers — test voltages, resistance and component values, torque figures, acceptance windows and pin assignments are referred to the manufacturer's documentation for your exact model rather than given here, because a plausible-looking figure for the wrong machine is more dangerous than no figure at all.

Direct technical answer

Check the settings before you check the hardware. On hybrid and inverter-charger units the single most common cause is configuration rather than failure: a charge-source priority set to solar-only so the unit deliberately ignores utility and generator, a charge current limit left at or near zero, or a battery profile that does not match the bank installed. After settings, the diagnosis splits three ways. Either the unit is not accepting its AC input — measure at the inverter's own AC input terminals and check frequency as well as voltage, because a generator that wanders outside the acceptance window is rejected exactly as a UPS would reject it. Or the charger is delivering and the battery cannot accept charge, which an aged bank will do while still showing a plausible resting voltage. Or, least often, the charging stage itself has failed. Establish which of the three before ordering any part.

01Symptom description

Controller / display

  • ▪Battery state of charge static or falling while an AC source is present
  • ▪No charging indication despite utility or generator being available
  • ▪Charging indicated but current shown as zero or negligible
  • ▪AC input not accepted, input out of range, or utility-fail indication
  • ▪Battery fault or battery-type mismatch warning

Indicators

  • ▪Charger LED off while the AC input LED is lit
  • ▪Both AC and charge indications absent
  • ▪Fault indication specific to the charging stage

Sounds

  • ▪Transfer relay clicking repeatedly as the unit accepts then rejects the AC source
  • ▪Charger cooling fan never running, which suggests the stage is not operating at all
  • ▪Gassing or bubbling from flooded cells, which indicates over-charging rather than under-charging

Smells

  • ▪Acid or sulphurous smell at the battery bank, indicating over-charging or a failing cell
  • ▪Hot electronics smell from the enclosure, which warrants immediate investigation

Behaviour

  • ▪Charges from the generator but not from utility, or the reverse, which points at input acceptance rather than the charger
  • ▪Charges only in strong sun on a hybrid, which is usually the charge-source priority setting
  • ▪Charges to a point then stops well short of full, which suggests the battery or the profile rather than the charger
  • ▪Charged normally until a settings change, firmware update or battery replacement
  • ▪Battery warm during charging, which suggests over-charging or an internal battery fault

Visible

  • ▪AC input breaker and fuse condition
  • ▪Battery terminal corrosion, tightness and cable condition
  • ▪Battery age labels and installation dates
  • ▪Temperature sensor presence and where it is mounted
  • ▪Any discolouration or heat marking around the AC input terminals

02What the fault means

In plain language

The inverter is not putting charge back into the batteries even though power is available. Often it has been told not to — by a setting that prefers solar, a charge limit turned down, or a battery type that does not match what is fitted. Sometimes it is refusing the incoming power because that supply is not good enough. Sometimes the batteries are simply too old to take a charge. The checks below separate those before anything is replaced.

Technical explanation

The charging stage is a constant-voltage source with a current limit, operating to a profile selected for the battery chemistry: typically a bulk phase at the current limit, an absorption phase at a held voltage, and a float phase. The unit will only run that profile if it has accepted an AC source, which requires the input to satisfy configured voltage and frequency acceptance criteria — engine-driven supplies fail these far more often than utility, because frequency excursions during load steps push the input outside the window. Charge-source priority on hybrid units determines whether utility or generator may charge at all, and setting it to solar-only produces a unit that is functioning exactly as configured while appearing faulty. Because a constant-voltage charger supplies whatever current the bank draws at the held voltage, and that current falls as the bank approaches full, low charging current is only meaningful when interpreted against state of charge: a healthy full bank legitimately draws almost nothing, while a genuinely discharged bank drawing nothing indicates a battery that can no longer accept charge. Temperature compensation, where fitted, adjusts the held voltage against battery temperature; a failed sensor produces chronic over- or under-charging that presents as premature battery failure rather than as a charger alarm.

03Common causes, ranked

These are ordered by likelihood. Presenting every possible cause as equally probable is a failure of diagnosis, not thoroughness.

Most likely

start here
  • ▪Charge-source priority configured to solar-only, so utility and generator are deliberately ignored
  • ▪Charge current limit set at or near zero
  • ▪AC input not accepted — frequency or voltage outside the configured window, commonly on generator supply
  • ▪Battery bank at end of life and no longer able to accept charge

Possible

check next
  • ▪Battery type or charge profile does not match the bank actually installed
  • ▪AC input breaker tripped or fuse open
  • ▪Loose or corroded battery terminals raising resistance in the charge path
  • ▪BMS on a lithium bank inhibiting charge for its own protective reasons

Less common

after the above
  • ▪Temperature compensation sensor failed, causing chronic under- or over-charging
  • ▪Charging stage within the unit failed
  • ▪Firmware or configuration corrupted after an update
  • ▪Battery bank of mixed ages, where older blocks limit the whole string

Model specific

verify per unit
  • ▪Charge-source priority, current limit and battery-profile options differ substantially between manufacturers and models — read them from the equipment
  • ▪Absorption and float voltages are chemistry-specific and configurable; take them from the battery documentation, never from a general figure
  • ▪Lithium banks charge under BMS control and the inverter may need a matching communication protocol selected
  • ▪Some units offer a wider input window or generator mode intended for engine-driven supplies
  • ▪Equalisation, where offered, must never be applied to a chemistry that does not permit it

Environmental

site conditions
  • ▪Battery space running hot, which is the dominant factor in shortening battery life
  • ▪Very low temperature reducing charge acceptance
  • ▪Dust or humidity causing terminal corrosion
  • ▪Unstable utility supply repeatedly falling outside the acceptance window

Installation related

built in
  • ▪Battery bank sized for energy alone without regard to charge and discharge rates
  • ▪Undersized or long DC cabling causing voltage drop that misleads the charger
  • ▪Temperature sensor not fitted, or mounted where it does not represent the battery
  • ▪Generator undersized for the combined site and charging load

Maintenance related

deferred work
  • ▪Battery capacity never tested, only terminal voltage checked
  • ▪Installation dates never recorded, so bank age is unknown
  • ▪Terminals never re-torqued
  • ▪Bank replaced block by block over time, mixing ages within one string

Component level

electronics
  • ▪Charging stage or its control failed
  • ▪Internal charger fuse open
  • ▪Temperature sensor open or short circuit
  • ▪Input relay or contactor failed, so the AC source is never connected through

04Safety requirements

Isolation

  • ▪The battery bank cannot be switched off and is live whenever connected
  • ▪Isolate the AC input, the DC and any solar source before working on the unit, then prove dead at the point of work
  • ▪A solar array is live in any daylight and cannot be switched off at source
  • ▪Confirm the DC bus has discharged before opening the enclosure

Lockout and tagout

  • ▪Lock and tag the AC input, the DC isolator and the array isolator
  • ▪Confirm with the site that the load may be unprotected during the work
  • ▪Keep the only key with the person doing the work

PPE

  • ▪Eye protection at all times near batteries
  • ▪Acid-resistant gloves and apron for lead-acid work
  • ▪Insulated tools rated for the DC system voltage
  • ▪Remove watches, rings and metal bracelets before battery work

Stored energy

  • ▪DC bus capacitors retain a dangerous charge after disconnection — verify with a meter rather than trusting a stated time
  • ▪The battery bank remains live at all times
  • ▪Lead-acid batteries vent hydrogen while charging; ventilate before working and remove ignition sources

Specific hazards

  • ▪A dropped tool across battery terminals will weld instantly and can rupture the battery
  • ▪DC arcs do not self-extinguish as AC arcs do
  • ▪Never work on a battery that is swollen, hot, leaking or damaged — isolate the area and escalate
  • ▪Never apply an equalisation or boost charge to a chemistry that does not permit it; this can destroy a bank and, with sealed batteries, cause venting or rupture

Stop and call a qualified professional if

  • ▪Any battery is swollen, hot, leaking or physically damaged
  • ▪There is a burnt smell or visible damage inside the unit
  • ▪The installation uses a lithium bank whose BMS behaviour you cannot interrogate
  • ▪Work requires opening the enclosure and you cannot verify the DC bus has discharged

05Tools required

Tools required and the reason each is needed
ToolWhy it is needed
True-RMS digital multimeterAC input at the inverter terminals and DC at the battery — the two measurements that split the diagnosis
Frequency-capable meter or power quality analyserGenerator frequency is a leading reason an AC input is rejected, and a voltage-only check misses it entirely
DC clamp meterActual charge current into the bank, which distinguishes a charger fault from a battery that cannot accept charge
Battery impedance analyser or capacity testerEstablishing whether the bank can still accept and hold charge; resting voltage will mislead you
Infrared thermometer or thermal cameraBattery and terminal temperature — heat is both a cause and a symptom
Insulated torque wrenchBattery and DC terminations must be torqued to specification
Access to the unit configuration interfaceCharge-source priority, current limit and battery profile are read and corrected here, and settings resolve a large share of these faults

06Diagnostic decision tree

Diagnostic decision flowchart: Inverter Not Charging Batteries — Diagnosis and RepairA 8-step decision flowchart. Each step asks a diagnostic question; answering yes continues down to the next question, while answering no leads to the stated finding. The same sequence is written out in full immediately below this diagram.1. Is any battery swollen, hot, leaking or damaged?Yes — Stop. Isolate the area and escalate.NoContinueYes2. Is the charge-source priority set to allow chargingfrom the available source?Yes — ContinueNoThe unit is behaving as configured.Correct the priority setting andre-test.Yes3. Is the charge current limit set to a usable value?Yes — ContinueNoA limit at or near zero producesexactly this symptomYes4. Is AC present at the INVERTER input terminals, withfrequency in the accepted window?Yes — ContinueNoThe unit is rejecting or not receivingthe source — this is an input problem,not a charger faultYes5. Does the battery profile match the bank actuallyinstalled?Yes — ContinueNoCorrect the profile; a mismatch causeschronic under- or over-chargingYes6. Is current flowing into the bank, and is the bankactually discharged?Yes — Charging is occurring — the concern is capacity orrate, not the chargerNoA discharged bank drawing no currentat correct voltage cannot acceptchargeYes7. Do all blocks show similar voltage and internalresistance?Yes — ContinueNoOne degraded block limits the wholestringYes8. With settings correct, AC accepted and a proven-goodbank, is charging still absent?Yes — The charging stage is genuinely faulty. Refer forworkshop diagnosis.NoFault resolved — complete validationand record the causeYesContinue to the step-by-step diagnosis below.
Diagnostic decision flow for inverter not charging batteries — diagnosis and repair. Simplified illustration — not a replacement for the manufacturer's model-specific schematic or service data. The same sequence is written out in full below.
  1. 1. Is any battery swollen, hot, leaking or damaged?

    Yes → Stop. Isolate the area and escalate.

    No → Continue

  2. 2. Is the charge-source priority set to allow charging from the available source?

    Yes → Continue

    No → The unit is behaving as configured. Correct the priority setting and re-test.

  3. 3. Is the charge current limit set to a usable value?

    Yes → Continue

    No → A limit at or near zero produces exactly this symptom

  4. 4. Is AC present at the INVERTER input terminals, with frequency in the accepted window?

    Yes → Continue

    No → The unit is rejecting or not receiving the source — this is an input problem, not a charger fault

  5. 5. Does the battery profile match the bank actually installed?

    Yes → Continue

    No → Correct the profile; a mismatch causes chronic under- or over-charging

  6. 6. Is current flowing into the bank, and is the bank actually discharged?

    Yes → Charging is occurring — the concern is capacity or rate, not the charger

    No → A discharged bank drawing no current at correct voltage cannot accept charge

  7. 7. Do all blocks show similar voltage and internal resistance?

    Yes → Continue

    No → One degraded block limits the whole string

  8. 8. With settings correct, AC accepted and a proven-good bank, is charging still absent?

    Yes → The charging stage is genuinely faulty. Refer for workshop diagnosis.

    No → Fault resolved — complete validation and record the cause

07Step-by-step diagnosis

Step 1Inspect the battery bank before anything else

Inspect
Physical condition, installation dates, terminal condition and temperature
Where
At the battery bank
Instrument
Inspection light, infrared thermometer
Expected result
No swelling, leakage or heat; terminals clean and tight; dates recorded
If the result is abnormal
A swollen or hot battery ends the diagnosis and becomes a safety matter. Installation dates alone frequently answer the question.
Next
Step 2

Safety: Do not disturb a swollen, leaking or damaged battery.

Step 2Read the configuration before touching hardware

Inspect
Charge-source priority, charge current limit, battery type and profile
Where
Unit configuration interface
Instrument
Display or service software
Expected result
Priority permits the available source; current limit usable; profile matches the bank
If the result is abnormal
This resolves a large share of these callouts with no tools at all. A hybrid set to solar-only is functioning exactly as configured.
Next
Step 3

Verify for your unit: The correct absorption and float voltages for the chemistry installed — take these from the battery documentation, never from a general figure.

Step 3Check AC input protection and presence

Inspect
AC input breaker, fuse and voltage at the inverter input terminals
Where
Inverter AC input terminals
Instrument
True-RMS multimeter
Expected result
Nominal AC present at the unit
If the result is abnormal
No AC at the terminals moves the fault upstream. Measure at the unit, not at a nearby socket on another circuit.
Next
Step 4

Step 4Check input frequency, especially on generator supply

Inspect
Input frequency and its stability through load changes
Where
Inverter AC input terminals
Instrument
Frequency-capable meter or analyser
Expected result
Frequency at nominal and steady
If the result is abnormal
Frequency wandering on load steps causes the unit to reject the source. That is a generator governing problem, not a charger fault, and adjusting the inverter to accept it treats the symptom.
Next
Step 5

Verify for your unit: The configured input acceptance window for this model — it differs between units and must be read from the equipment.

Step 5Measure charge current and interpret against state of charge

Inspect
Actual DC current flowing into the bank
Where
Battery cable, using a DC clamp
Instrument
DC clamp meter
Expected result
Substantial current into a discharged bank, tapering as it approaches full
If the result is abnormal
Low current alone is not a fault — a full bank legitimately draws almost nothing. Low current into a genuinely discharged bank is the finding that matters, and it indicts the battery.
Next
Step 6

Safety: Use a DC clamp. An AC-only clamp reads nothing useful here.

Step 6Measure per-block voltage and internal resistance

Inspect
Each block across the bank
Where
At each block in turn
Instrument
Multimeter and battery impedance analyser
Expected result
All blocks within a narrow band of each other
If the result is abnormal
One block markedly different limits the whole string. Rising internal resistance appears well before terminal voltage reveals anything.
Next
Step 7

Verify for your unit: Acceptable internal resistance for the specific battery type — an absolute figure means little without the manufacturer reference or a commissioning baseline.

Step 7Check temperature compensation and the DC path

Inspect
Compensation sensor health and mounting; voltage drop and heat along the charge path
Where
At the sensor and across every DC termination
Instrument
Multimeter, thermal camera, torque wrench
Expected result
Sensor healthy and representative; joints cool and torqued to specification
If the result is abnormal
A failed sensor causes chronic over- or under-charging. A high-resistance joint makes the charger see a voltage the battery never receives, so it terminates charging early.
Next
Step 8

Step 8Confirm BMS permission on lithium banks

Inspect
Whether the BMS is permitting charge, and whether the communication protocol matches
Where
BMS interface and inverter configuration
Instrument
BMS software or display
Expected result
BMS permitting charge and communicating correctly with the inverter
If the result is abnormal
A BMS may inhibit charging for temperature, cell imbalance or protection reasons the inverter reports only as a generic fault.
Next
Step 9

Step 9Only now conclude the charging stage has failed

Inspect
Whether charging is absent with correct settings, an accepted AC input and a proven-good bank
Where
At the unit
Instrument
All prior measurements
Expected result
All external and configuration causes eliminated first
If the result is abnormal
A unit that will not charge a proven-good bank from an accepted source has a genuine internal fault. Conclude this last, not first.
Next
Refer for workshop diagnosis with measurements recorded

08Repair procedure

Settings — check these first

configuration
  • ▪Set charge-source priority to permit the sources the site actually has
  • ▪Set a usable charge current limit appropriate to the bank capacity
  • ▪Select the battery type and profile that matches the bank installed
  • ▪Where a lithium BMS communicates with the inverter, select the matching protocol
  • ▪Enable and verify temperature compensation where fitted

A large share of these faults are resolved here, with no parts and no disassembly.

Charge path integrity

cleaning and connections
  • ▪Clean corroded terminals and re-torque every DC joint to specification
  • ▪Replace undersized or overheated DC cabling
  • ▪Mount the temperature sensor where it genuinely represents the battery

Battery bank

component replacement
  • ▪Replace a bank at end of life as a complete matched set
  • ▪Never mix new blocks with old — the old blocks drag the new ones down and the fault returns within months
  • ▪Record installation dates and take a commissioning impedance baseline
  • ▪Dispose of removed batteries through a licensed route

Battery environment

mechanical
  • ▪Improve ventilation or provide cooling where the battery space runs hot
  • ▪Fit temperature monitoring so the environment is visible rather than assumed

Charging stage

manufacturer level
  • ▪Refer charging stage and control faults to the manufacturer or a properly equipped facility
  • ▪Provide the measured voltages, currents and configuration, which shortens the repair considerably

09Post-repair validation

  • ▪Confirm the unit accepts the AC source and enters a charging phase
  • ▪Confirm charge current is present and tapers correctly as the bank approaches full
  • ▪Confirm the held voltage matches the profile for the chemistry installed
  • ▪Record per-block voltage and internal resistance as a new baseline
  • ▪Prove real autonomy with a timed discharge where capacity is in question
  • ▪Re-torque and thermally survey every DC joint under load after the work
  • ▪Record the settings changed, the measurements taken and the cause identified

10When not to repair

  • ▪A bank at or beyond service life — replacement is the fix, and further charger investigation is wasted effort
  • ▪Any battery showing swelling, leakage or heat damage
  • ▪Banks partially replaced over time, producing a mixed-age set that will never perform
  • ▪Obsolete units where charging boards and firmware are unobtainable
  • ▪Where the battery environment cannot be brought within specification, since a new bank will simply repeat the failure

11Prevention

  • ▪Record the commissioned configuration so an unintended settings change is detectable
  • ▪Test battery capacity annually rather than relying on terminal voltage
  • ▪Take an impedance baseline at commissioning and trend against it
  • ▪Keep the battery space ventilated or cooled; heat is the dominant life factor
  • ▪Re-torque DC terminations at every service visit
  • ▪Replace banks as complete matched sets, planned at end of design life rather than at failure
  • ▪Where a generator charges the bank, confirm its frequency stability under load rather than assuming it

12Questions engineers actually ask

It charges from solar but never from the generator. Is the charger faulty?

Usually not. Check two things first: the charge-source priority setting, which on many hybrids is set to solar-only and makes the unit ignore other sources by design; and the generator's frequency stability, because a set that wanders on load steps is rejected by the input acceptance criteria. Both are common and neither is a charger fault.

The charger shows almost no current. Does that mean it has failed?

Only if the bank is genuinely discharged. A constant-voltage charger supplies whatever current the bank draws at the held voltage, and that falls to almost nothing as the bank fills. Low current into a full bank is correct behaviour; low current into a flat bank means the battery can no longer accept charge.

Can I set a higher charge voltage to force more charge in?

No. The absorption and float voltages are properties of the chemistry, not preferences. Raising them over-charges the bank, drives water loss and heat, and with sealed batteries can cause venting or rupture. If the bank will not take charge at the correct voltage, the bank is the problem.

Why did charging stop working right after we replaced the batteries?

Almost always the battery profile. A new bank of a different chemistry or capacity needs the charge profile, current limit and, on lithium, the communication protocol reselected. The unit is charging to the old bank's rules, which the new bank either refuses or cannot use.

Standards and references

  • ▪IEC 62109-1 and IEC 62109-2 — safety of power converters for use in photovoltaic power systems
  • ▪IEC 62040-1 — UPS general and safety requirements, where the unit performs a UPS function
  • ▪IEEE 1188 — recommended practice for maintenance, testing and replacement of VRLA batteries
  • ▪EN 50272-2 — safety requirements for secondary batteries and battery installations
  • ▪The inverter and battery manufacturer's documentation for the specific units, which gives the charge profile voltages, acceptance windows and torque figures referred to throughout

This guidance is written from engineering principle and is not a substitute for the manufacturer's model-specific documentation. Where a figure is model-specific, confirm it against the service data for your unit before acting on it.

Need this diagnosed properly?

Send us the make, model and any fault codes shown, and photographs of the controller display if you have them. Our mobile workshop covers all 47 counties.

Call 0768860665WhatsApp the fault detailsRequest a site inspection